a) Explain how drooping characteristics cater for stable operation when running in parallel. (6) b) Two shunt generators X and Y work in parallel. Their external characteristics may be assumed to be a linear over their normal working range the terminal voltage of X falls 265V on no load 230V when delivering 350Ato the busbars, while the voltage of Y falls from 270 V on no load to 240V when delivering 400A to the bus bars. Calculate the current with each machine delivers when they share a common load of 500A. what is thw bus bar voltage under this condition and the power delivered by each machine